Schneider 3 phase Zelio RM 24V 5A 8A Detection Module DC Voltage Control Relay
5a 8a control relay module 24vdc zelio dc voltage controlled relay
schneider 24v 1c/o IP20 IP40 IP50 3 phase voltage control relay
schneider 2c/o resistive probes 24-480VAC detection dc relay control
range of product
|
Zelio Control
|
product or component type
|
Modular measurement and control relays
|
relay type
|
Level control relay
|
relay name
|
RM22L
|
relay monitored parameters
|
Detection by resistive probes
|
time delay type
|
Without
|
switching capacity in VA
|
2000 VA
|
measurement range
|
5...100 kOhm
|
reset time
|
1750 ms
|
maximum switching voltage
|
250 V AC
|
minimum switching current
|
10 mA at 5 V DC
|
maximum switching current
|
8 A AC
|
[Us] rated supply voltage
|
24...240 V AC/DC 50/60 Hz
|
supply voltage limits
|
20.4…264 V AC/DC
|
operating limits
|
- 15 % + 10 % Un
|
power consumption in VA
|
5 VA AC
|
maximum power consumption in W
|
1.5 W DC
|
output contacts
|
2 C/O
|
nominal output current
|
8 A
|
run-up delay at power-up
|
0.6 s
|
maximum electrode voltage
|
12 V AC
|
maximum electrode current
|
1 mA
|
repeat accuracy
|
+/- 2 % for time delay
|
measurement error
|
< 1 % over the whole range with voltage variation
0.05 %/°C with temperature variation |
sensitivity scale
|
5...100 kOhm St (Standard Sensitivity)
|
sensitivity adjustment
|
5…100 %
|
maximum supply current for sensors
|
1 mA
|
maximum cable distance between devices
|
1000 m between probe and delay
|
cable capacitance
|
1 nF at HS (High Sensitivity) for probe cable
2.2 nF at St (Standard Sensitivity) for probe cable 4.7 nF at LS (Low Sensitivity) for probe cable |
overvoltage category
|
III conforming to IEC 60664-1
|
insulation resistance
|
> 100 MOhm at 500 V DC conforming to IEC 60255-27
|
insulation
|
Between supply and measurement
|
mounting position
|
Any position
|
connections - terminals
|
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end |
tightening torque
|
0.6…1 N.m conforming to IEC 60947-1
|
housing material
|
Self-extinguishing plastic
|
status LED
|
LED (yellow)relay ON:
LED (green)power ON: |
mounting support
|
35 mm DIN rail conforming to EN/IEC 60715
|
electrical durability
|
100000 cycles
|
mechanical durability
|
10000000 cycles
|
utilisation category
|
AC-15 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1 AC-1 conforming to IEC 60947-4-1 DC-1 conforming to IEC 60947-4-1 |
safety reliability data
|
B10d = 120000
MTTFd = 125.5 years |
contacts material
|
Cadmium free
|
width
|
22.5 mm
|
net weight
|
0.1 kg
|
immunity to microbreaks
|
100 ms DC
90 ms AC |
electromagnetic compatibility
|
Immunity for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-1
Immunity for industrial environments conforming to EN/IEC 61000-6-2 Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 Emission standard for industrial environments conforming to EN/IEC 61000-6-4 Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4 Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5 Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 Conducted and radiated emissions class B group 1 conforming to CISPR 11 Conducted and radiated emissions class B conforming to CISPR 22 |
standards
|
EN/IEC 60255-1
|
product certifications
|
GL
RCM CCC CSA UL China RoHS EAC CE |
ambient air temperature for storage
|
-40…70 °C
|
ambient air temperature for operation
|
-20…50 °C at 60 Hz
-20…60 °C at 50 Hz AC/DC |
relative humidity
|
93…97 % at 25…55 °C conforming to IEC 60068-2-30
|
vibration resistance
|
0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6
1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 |
shock resistance
|
15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27
5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 |
IP degree of protection
|
IP20 (terminals) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529 |
pollution degree
|
3 conforming to IEC 60664-1
|
dielectric test voltage
|
2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27
|